GENERAL

 

Technical Description
The BSR-100X series of Analogue Addressable Fire Alarm Panels consists of 3 models(1,2 and 4 loop connections), named BSR-1001, BSR-1002 and BSR-1004 respectively, all sharing the same control interface, functionality and indications. The accompanying software application for Windows PC, BSR-100Xprovides utilities for calculating installation parameters, configuring the control panel and keeping an event log record.All BSR-100X models include 4 outputs for conventional sirens, an alarm relay, a fault relay and a programmable auxiliary relay.Two 12V lead acid (Pb) batteries are required in each control panel. The supported battery capacity is 7Ah, 9Ah, 12Ah or 15Ah, which must be calculated in accordance with the size of the installation (number of devices) and the required emergency duration (during mains interruption).
It is always recommended to use the “Battery Calculator” tool (included in BSR-100X software app) to calculate the required battery capacity according to your installation needs.The available loop output connections are: 1 for BSR-1001, 2 for BSR-1002 and 4 for BSR-1004. Each loop output connection can support up to 150 addressable units (smoke and heat detectors, addressable sirens, manual fire call points, etc).The “Loop Calculator” tool (included in BSR-100X software app) shall be used for cable selection according to your installation size.
All features and indications are in accordance with European standards ΕΝ54-2 and ΕΝ54-4.
The BSR-100Xseries Analogue Addressable Fire Alarm Panels is ideal for medium to large scale facilities such as department stores, hotels and factories.
An extended variety of settings and functionalities for controlling the fire alarm system (such as sirens, output relays and other) under certain events (by zone or task), is available via the software BSR-100x (for Windows PC). The communication between PC and control panel is via a USB cable
Operating Principles
Produced in accordance with EN54-2, EN54-4.

128 zone capability.

Auto-addressing capabilities.

220-240V AC mains power supply.

It offers 4 fully monitored siren outputs with a rating of 24V / 0,3A  and 1 programmable relay, as well as 8 extra relays.

Incorporated power supply with a rating of  24V/100W and built-in battery charger for 24V batteries with a capacity of up-to 15Ah.

The panels offer an extensive list of adjustments and characteristics for the control of the installed devices and sirens. These parameters can easily be adjusted using a PC based program.

The programming of the panel can also be done through an onboard USB.

Messages can be viewed on LCD display whereas LEDs are used to show basic operations such as alarms, pre alarms and faults.

The operation is done using the built-in 11 key keypad.

There is also an incorporated safety lock.

The maximum delay for the sirens is 10 minutes.

Optional Ethernet control capability.

Optional modbus expansion.

Optional external printer expansion.

Important notes

Besides the addressable sirens attached on the loop there is the ability to connect extra conventional sirens outputs or connect only conventional sirens.

 

 

 