Technical Description
The BSR-6155 is an analogue addressable smoke detector which integrates the function of optical smoke detection and it can work with any fire panel supports Olympia A Protocol. It can be adjusted to detect multiple levels of smoke offering flexibility and rich functionality. Also, it integrates a short circuit isolation circuit which is automatically activated and disconnects the defective node from the remaining loop, allowing it to be located by the panel.
Additional features of the device
– Integration of dynamic algorithms for noise and false alarm rejection.
– Dust compensation and automatic generation of cleaning notifications. Stable level of detection regardless of detector’ s working hours.
– Compensation of smoke measurements based on ambient temperature which ensures high  precision measurements even under extreme environmental conditions.
– Automatic fault diagnosis.
– Adjustable smoke alarm level for maximum flexibility.
– 360° optically visible LED.

Important notes

After installation the device must not be covered with dust or be painted or anything else happen that will block the smoke to get to the sensor. Special attention must be given during the installation and the use of the device, since the user assumes full responsibility for proper operation afterwards.

 

Type BSR-6155
Communication Protocol Olympia A Protocol
Main Voltage 11-30V DC
Standby Consumption 140μA
Alarm Consumption 2.5mA (with activated LED)
Smoke Concentration Sensitivity Adjustable from 0.107 to 0.300 in 0.010 dB/m steps
Indicators Alarm LED
Output Remote LED driver
Maximum Loop Current (lc max, -L in/out) 1A
Maximum Switch Current(ls max, -L in/out) 5A
Maximum Series Resistance (Zc max, -L in-out) 100mΩ
Maximum Leakage Current in Isolation Mode (lt max, -L in/out) 25mA pulses (6ms duration every 2 sec)
Isolation Voltage (Vso min-max) 9.3 – 10.6
Reconnect Voltage(Vsc min-max) 10.7 – 12.7
Degrees of Cover Protection IP42
Produced in accorandance with EN 54-7, EN-54-17
Operating temperature range -40 to 70°C
Relative Humidity Up to 95%
Construction Materials ABS/PC
External Dimensions 103(d) x 48(h) mm
Typical Weight 160gr.
Guarantee 2 years

 

Connection drawing
Connection drawing
Installation drawing
Installation drawing
Categories: ,

There are no reviews yet.

Be the first to review “Addressable detectors”