Technical Description
BSR-5136 is an addressable manual call point which activates the fire detection panel.BSR-5136 works with any panel supports Olympia A Protocol. It is essential to be placed in every fire detection system in co-operation with fire detection. At least one manual call pointhas to be placed in every fire detection system, close to the main control panel.
Pushing the clear plastic cover of the manual call point activates the alarm system.The clear plastic cover does not break but can be reset to its original position using the special plastic key which is included in the package.Periodic fire detection system testing can be carried out by activating a manual call point. It should be mounted in a clearly visible spot, near to the exit or ladder and at a height of 1.5 meters.
Additional specifications
– Resettable operating element with easy front access
– 160° viewable LED
– Semi flush or surface mounting
– Configurable as alarm or pre-alarm call point

Imporant Note

BSR-5136 features an intergrated short-circuit isolator which is automatically activated to isolate the faulty node from the rest of the loop. This feature allows to locate installation faults directly from the main panel.

 

Type BSR-5136
Communication Protocol Olympia A Protocol
Main Voltage 11-30V DC
Standy Consumption 90μA
Alarm Consumption 2.5mA (με το LED αναμμένο)
Type Type A
Use Σε εσωτερικούς χώρους
Maximum loop current (Ic max, -L in/out) 1A
Maximum switch current (ls max, -L in/out) 5A
Maximum series resistance (Zc max, -L in-out 50mΩ
Maximum leakage current (lt max, -L in/out) 25mA pulses (6ms/2 sec)
Isolation voltage (Vso min-max) 9.3 – 10.6
Reconnect voltage (Vsc min-max) 10.7 – 12.7
Degrees of cover protection IP20
Produced in accordance with EN 54-11, EN-54-17
Operation temperature range -40 to 70°C
Relative Humidity Up to 95%
Construction materials ABS/PC
External dimensions 94 x 98 x 56 mm
Typical weight 185gr.
Guarantee 2years

 

 

 